PG vs metric gland threads: the difference and which to choose

In short

PG and metric are two separate thread standards for cable glands, and they do not fit each other. New designs use metric threads; for existing enclosures with PG entries, choose a PG gland or an adapter.

Two standards, two thread profiles

PG (Panzergewinde) is an older thread standard of German origin with an 80° thread angle. Metric threads have a 60° angle and, on cable glands, a 1.5 mm pitch (M12×1.5 to M63×1.5). Because the profiles differ, PG and metric threads do not fit each other.

The same body size in both threads

PGMetric
Pg 7M12×1.5
Pg 9M16×1.5
Pg 11M16×1.5
Pg 16M20×1.5
Pg 21M25×1.5
Pg 29M32×1.5
Pg 36M40×1.5
Pg 42M50×1.5
Pg 48M63×1.5

Which should you choose?

  • For new enclosure and machine designs, choose metric threads.
  • For enclosures whose existing entries are PG, use PG glands.
  • Where you need to move between the two, fit a metric–PG adapter.

Related products

More articles

  • Guide5 min read

    How to choose a flexible steel conduit

    Four questions decide the right flexible steel conduit: ambient temperature, exposure to water and dust, electromagnetic interference, and cable size. Temperature picks the material, sealing picks the coating, interference picks the braid, and the cable bundle picks the diameter.

  • Technical4 min read

    What does IP68 mean? IP ratings explained

    In an IP code the first digit is protection against dust and solid objects, the second against water. IP68 means fully dust-tight and able to withstand continuous immersion.